2.1.5. Reset
Two Reset options are available via SIMATIC PDM. Selecting Factory Default 
resets all parameters excluding device addresses to default values. Device Reset 
(Warm Start ) has the same effect as recycling power. Only Factory Default is 
available via the handheld programmer.
To perform a Reset via the handheld programmer:
a. Press Mode to open PROGRAM mode, and key in 215 for Quick Access, or use 
ARROW keys to navigate to Reset.
b. Press RIGHT Arrow to open Edit Mode.
c. Press DOWN Arrow to scroll to PARAMS and RIGHT Arrow to select it. After 
the Reset is performed, the display will return to NONE.
d. Press Mode to return to Measurement Mode.
To perform a Reset via SIMATIC PDM:
Open the menu Device – Reset, and select Factory Defaults or Device Reset (for 
more detail see 
Reset Fault
Resets the Fault message after an active fault has occurred and been corrected. 
This is required only for faults listed as requiring a manual reset in the General 
Fault Code list (see page 80).
Open the menu View – Clear Faults. You will see the fault listed. Click Transfer.
To reset via the handheld programmer, key in the value of the fault code in 
question.
Notes: 
• After resetting to Factory Defaults, complete reprogramming is required.
• Resetting to Factory Defaults does not clear values in the Quick Start Wizard: 
they can be re-applied. 
• Performing a Device Reset clears all values from the Quick Start Wizard.
HART
PROFIBUS 
Description
Handheld 
Program-
mer 
Options
PARAMS
PARAMS
Factory Defaults
WARMSTART Device Reset: restarts the device (this 
option is rarely used).
ADDRESS
Reset PROFIBUS address to 126.
NONE
NONE
No reset performed.