Siemens LR 460 User Manual
Page 46
SITRANS LR 460 – INSTRUCTION MANUAL
7ML19985JM01
mmmmm
Pa
ra
m
e
te
rs
2. Identification
Operation Unit
Tag
Text that can be used in any way, for example as a unique label for a field device
in the plant.
Description
Text that is associated with the Field Device. This text can be used by the user in
any way. There is no specific recommended use.
Message
Text that is associated with the Field Device. This text can be used by the user in
any way. There is no specific recommended use..
2.1. Configuration
2.1.2. Address
The unique address of the device on the network (PROFIBUS or HART address).
To set the address via the handheld programmer:
• Press Mode
to
activate
PROGRAM mode, menu item 1.0.
• Press Down ARROW
, Right ARROW ,
Right ARROW
to navigate to
Address.
• Press Right ARROW
to open Edit mode: the PROGRAM icon will flash.
• If required, key in a new value and press Right ARROW
to accept it.
To set Address via PDM (PROFIBUS PA only):
Open the menu Device – Set Address.
2.1.3. Remote operation enable (REMLOCK)
Enables or disables programming via the network and PDM.
Note:
Default settings in the parameter tables are indicated with an asterisk (*) unless
explicitly stated
Values
PROFIBUS PA
0 - 126, default: 126 (We recommend a setting in the range
1 to 125.)
1 to 125.)
HART
0 to 15,default: 0
Handheld programmer
Values
Values
0
*
Remote operation enabled
1
Remote operation disabled