Siemens LR 460 User Manual
7ML19985JM01
SITRANS LR 460 – INSTRUCTION MANUAL
Page 45
mmmmm
Pa
ra
ra
m
e
te
rs
1.4. Units
Select the units for the Quick Start variables (high and low calibration point, and
level, distance, or space).
1.5. High Calibration Point
Distance from Sensor Reference to High Calibration Point: usually process full
level (see illustration to 1.3)
1.6. Low Calibration Point
Distance from Sensor Reference to Low Calibration Point: usually process empty
level (see illustration to 1.3)
1.7. Rate
Sets the reaction speed of the device to measurement changes in the target
range.
Use a setting just faster than the maximum filling or emptying rate (whichever is
greater). Slower settings provide higher accuracy: faster settings allow for more
level fluctuation
greater). Slower settings provide higher accuracy: faster settings allow for more
level fluctuation
1.8. Apply Changes
In order to save the settings changed in the Quick Start wizard it is necessary to
enable Apply Changes.
Options
mm, cm, m, in, ft
Values
Range: 0.0000 to 100.00 m
Values
Range: 0.0000 to 100.00 m
Options
SLOW
0.1 m/minute
MED
1.0 m/minute
FAST
10.0 m/minute
Options
YES, NO