GE 1018959 User Manual

Page of 24
4  CONFIGURATION 
 
4.1  CONFIGURATION METHODS 
The SNMP/Web plug-in adapters can be configured using different interfaces. 
 
4.1.1  Configuration via serial connection  
• 
Connect the SNMP adapter to a computer using a standard 1:1 serial communication cable.  
• 
Run a terminal simulator (e.g. HyperTerminal on a PC running Windows) 
• 
Configure the terminal simulator as follows: 
115,200bps,   8 data bits,   1 stop bit, 
 parity 
none, flow 
control 
none 
Terminal emulation VT-100 
 
 
 
• 
Establish the connection and press <enter> 
• 
The default username (login) and password are ge and ge 
• 
A command-line configuration interface is entered. Type menu to enter the quick network 
configuration menu: 
 
Modifications reserved 
Page 19/24 
ISG_CNT_SNM_BAS_CRD_1GB_V012.doc 
Installation Guide SNMP/Web Adapter