Chapter 8  Diagnostics and Fault Clearing
Display and Clear Faults from Logicmaster 5 or Logicmaster 6 
If the host CPU is a Series Five or Series Six PLC, faults from a remote drop are
displayed in the Genius Fault Table.  A Logicmaster 6 fault table is illustrated below.
The Logicmaster 5 fault table is similar.
Faults from remote drops are identified as GENA faults.  The GENA is the component
within the Remote I/O Scanner that handles the Genius bus interface.
                                                       L/M: OFFLINE
      TOTAL FAULTS: 0000          GENIUS I/O FAULT TABLE               date
      TOP FAULT DISPLAYED:0000                                         time
      FAULT DISPLAYED:                                      0000:00:00:00:0
   B/C   POINT  CIRC      FAULT        FAULT        FAULT 
   ADDR. ADDR.  NO.      CATEGORY      TYPE      DESCRIPTION   DAY:HR:MN:SC:T
   ––––– –––––– –––– –––––––––––––––– –––––––– ––––––––––––––– –––––––––––––––
   0 0   I0001   1   CIRCUIT FAULT    DISCRETE   OPEN WIRE     147:12:03:12:44 
   0 64  O0053   6   CIRCUIT FAULT    DISCRETE   NO LOAD       147:13:56:31:04
   1 32  IO001                        GENA                     148:03:12:48:55
                                                                               
 
    
NEXT    PREV   CLEAR                                         XPNDED
 
 1 
PAGE
  2 
PAGE
  3
FAULTS
 4 
TOP
         5
BOTTOM
 6       7       8 
FUNC
Fault Clearing
Pressing the Clear Faults key clears all faults currently in the fault table.  This sets the
fault count to zero, and sends a Clear command to the Remote I/O Scanner.