Series 90–70 Remote I/O Scanner User’s Manual – July 1992
120
Status References 
Status references in the Remote I/O Scanner are assigned to %S, %SA,  %SB, and %SC
memory.  These references have the same definitions as the status references for the
Series 90–70 PLC, although not all are meaningful for a Remote I/O Scanner.  They can
be monitored using the reference tables function of Logicmaster 90 with the
programmer communicating with the remote drop.
Reference
Nickname
Definition
%S0001
FST_SCN
Current sweep is the first sweep.
%S0003
T_10MS
0.01 second timer contact.
%S0004
T_100MS
0.1 second timer contact.
%S0005
T_SEC
1.0 second timer contact.
%S0006
T_MIN
1.0 minute timer contact.
%S0007
ALW_ON
Always ON.
%S0008
ALW_OFF
Always OFF.
%S0009
SY_FULL
Set when the Remote I/O Scanner’s PLC Fault Table fills up.   Cleared when an entry is re-
moved from the PLC Fault Table and when the PLC Fault Table is cleared.
%S0010
IO_FULL
Set when the Remote I/O Scanner’s I/O Fault Table fills up.  Cleared when an entry is re-
moved from the I/O Fault Table and when the I/O Fault Table is cleared.
%S0011
OVR_PRE
Set when an override exists in %I or memory.
%SA0009
CFG_MM
Set when a configuration mismatch is detected during power–up or during a store of the
configuration.  Cleared by powering up the Remote I/O Scanner when no mismatches are
present or during a store of configuration that matches hardware.
%SA0010
HRD_CPU
Set when the diagnostics detects a problem with the Remote I/O Scanner hardware.  Cleared
by replacing the Remote I/O Scanner.
%SA0012
LOS_RCK
Set when an expansion rack in the remote drop stops communicating with the communicat-
ing with the Remote I/O Scanner.  Cleared by fixing the problem and power cycling the rack.
%SA0014
LOS_IOM
Set when an I/O module stops Remote I/O Scanner.  Cleared by replacing the module and
cycling power on the rack containing the module.
%SA0015
LOS_SIO
Set when an option module stops communicating with the Remote I/O Scanner.  Cleared by
replacing the module and cycling power on the rack containing the module.
%SA0017
ADD_RCK
Set when an expansion rack is added to the remote drop.  Cleared by cycling power on the
rack containing the module and when the con figuration matches the hardware after a store.
%SA0019
ADD_IOM
Set when an I/O module is added to a rack.  Cleared by cycling power on the rack containing
the module and when the configuration matches the hardware after a store.
%SA0020
ADD_SIO
Set when an option module is added to a rack.  Cleared by cycling power on the rack contain-
ing the module and when the configuration matches the hardware after a store.
%SA0023
IOM_FLT
Set when an I/O module reports a circuit or module fault.  Cleared by cycling power on the
rack containing the module and when the config uration matches the hardware after a store.
%SA0027
HRD_SIO
Set when a hardware failure is detected in an option module.  Cleared by replacing the mod-
ule and cycling power on the rack containing the module.
%SA0032
SBUS_ER
Set when a bus error occurs on the VME bus backplane.  Cleared by cycling power on rack 0.
%SB0010
BAD_RAM
Set when the Remote I/O Scanner detects corrupted RAM memory  at  power–up.    Cleared
when the Remote I/O Scanner detects that RAM memory is valid at power–up.
%SB0013
SFT_CPU
Set when the Remote I/O Scanner detects an unrecoverable error in the software.  Cleared by
cycling power to the Remote I/O Scanner.
%SB0014
STOR_ER
Set when an error occurs during a programmer store operation.  Cleared when a store opera-
tion is completed successfully.
%SB0017
SBUS_FL
Set when the Remote I/O Scanner fails to gain access to the bus.  Cleared by cycling power on
the rack 0.
%SC0009
ANY_FLT
Set when any fault occurs.  Cleared when both fault tables have no entries.
%SC0010
SY_FLT
Set when any fault occurs that causes an entry to be placed in the Remote I/O Scanner’s PLC
Fault Table.  Cleared when the PLC Fault Table has no entries.
%SC0011
IO_FLT
Set when any fault occurs that causes an entry to be placed in the Remote I/O Scanner’s I/O
Fault Table.  Cleared when the I/O Fault Table has no entries.
%SC0012
SY_PRES
Set as long as there is at least one entry in the Remote I/O Scanner’s PLC fault table.  Cleared
when the PLC fault table has no entries.
%SC0013
IO_PRES
Set as long as there is at least one entry in the Remote I/O Scanner’s I/O fault table.  Cleared
when the I/O fault table has no entries.
%SC0014
HRD_FLT
Set when a hardware fault occurs.  Cleared when both fault tables have no entries.
%SC0015
SFT_FLT
Set when a software fault occurs.  Cleared when both fault tables have no entries