6  Commissioning 
MICROMASTER 440   
Operating Instructions (Compact) 
63
 
6.4.18.9 PID 
controller 
 
BI: Enable PID controller
PID mode Allows user to enable/disable the PID controller. Setting to 1 enables the PID 
controller. Setting 1 automatically disables normal ramp times set in P1120 and P1121 and 
the normal frequency setpoints.
 
PID
 mode 
Configuration of PID controller. 
  0  PID as setpoint 
  1  PID as trim 
 
CI: PID setpoint 
Defines setpoint source for PID setpoint input. 
 
CI: PID trim source 
Selects trim source for PID setpoint. This signal is multiplied by the trim gain and added to 
the PID setpoint. 
 
Ramp-up time for PID setpoint
Sets the ramp-up time for the PID setpoint.
 
Ramp-down time for PID setpoint
Sets ramp-down time for PID setpoint.
 
CI: PID feedback 
Selects the source of the PID feedback signal.
 
Max. value for PID feedback
Sets the upper limit for the value of the feedback signal in [%]..
 
P2268 =... 
 
Min. value for PID feedback
Sets lower limit for value of feedback signal in [%]..
 
CO: PID
 error 
Displays PID error (difference) signal between setpoint and feedback signals in [%]. 
 
PID derivative time 
Sets PID derivative time. 
P2274 = 0: 
The derivative term does not have any effect (it applies a gain of 1). 
 
PID proportional gain 
Allows user to set proportional gain for PID controller.
 
PID integral time 
Sets integral time constant for PID controller.
 
PID output upper limit 
Sets upper limit for PID controller output in [%].
 
P2292 =... 
 
PID output lower limit 
Sets lower limit for the PID controller output in [%]. 
 
0.0
 
0.0
 
0.0
 
1.00 s
 
1.00 s
 
755.0
 
100.00 %
0.00 %
3.000
 
0.000 s
100.00 %
0.00 %
 
P2291 =... 
 
P2285 =... 
 
P2280 =... 
 
r2251 =... 
0.000 
 
P2274 =... 
 
r2273 =... 
 
P2200 =... 
 
P2253 =... 
 
P2254 =... 
 
P2257 =... 
 
P2258 =... 
 
P2264 =... 
 
P2267 =...