6  Commissioning 
MICROMASTER 440   
Operating Instructions (Compact) 
61
 
6.4.18.8 
Load torque monitoring 
This function monitors the transmission of force between a motor and driven load 
within a defined frequency range. Typical applications include, for example, 
detecting when a transmission belt breaks or detecting when a conveyor belt is in 
an overload condition. 
For the load torque monitoring, the actual frequency/torque actual value is 
compared to a programmed frequency/torque characteristic (refer to P2182 – 
P2190). Depending on P2181, the system monitors whether the permissible torque 
curve is either exceeded or fallen below. If the actual value lies outside the 
tolerance bandwidth, then after the delay time P2192 has expired, either alarm 
A0952 is output or fault F0452. 
 
 
Belt failure detection mode 
Parameter P2181 activates or de-activates the load torque monitoring and defines the 
response to a load torque fault. 
  0  Belt failure detection disabled 
  1  Warning: Low torque / frequency 
  2  Warning: High torque / frequency 
  3  Warning: High / low torque / frequency 
  4  Trip: Low torque / frequency 
  5  Trip: High torque / frequency 
  6  Trip: High / low torque / frequency 
 
Belt threshold frequency 1 
Sets a frequency threshold 1 for comparing actual torque to torque the envelope for belt 
failure detection. 
 
Belt threshold frequency 2 
Sets a frequency threshold 2. 
 
Belt threshold frequency 3 
Sets a frequency threshold 3. 
 
Upper torque threshold
 
Upper limit threshold value 1 for comparing actual torque. 
 
Lower torque threshold
 
Lower limit threshold value 1 for comparing actual torque. 
 
Upper torque threshold
 
Upper limit threshold value 2 for comparing actual torque. 
 
Lower torque threshold
 
Lower limit threshold value 2 for comparing actual torque. 
 
Upper torque threshold
 
Upper limit threshold value 3 for comparing actual torque. 
 
Lower torque threshold
 
Lower limit threshold value 3 for comparing actual torque. 
 
Time delay for belt failure 
P2192 defines a delay before warning/trip becomes active. It is used to eliminate events 
caused by transient conditions. It is used for both methods of fault detection. 
P2181 = ... 
P2182 = ... 
5.00 
P2183 = ... 
30.00 
P2184 = ... 
50.00 
P2185 = ... 
99999.0
P2186 = ... 
0.0 
P2187 = ... 
99999.0
P2188 = ... 
0.0 
P2189 = ... 
99999.0
P2190 = ... 
0.0 
P2192 = ... 
10 
99999.0
99999.0
0.0 
0.0