SITRANS LR 460 – INSTRUCTION MANUAL
7ML19985JM01
mmmmm
Pa
ra
m
e
te
rs
4.1.8.5. Limit Hysteresis
Hysteresis is used to adjust the sensitivity of the trigger for alarm 
messages. It is used to compensate when a process variable fluctuates 
around the same value as a limit. A high level alarm occurs when a value 
exceeds an upper limit. The alarm’s status remains true until the value 
drops below the limit minus the alarm hysteresis. The directions are 
reversed for low limit detection.
Enter a value for the hysteresis here, to be used for all warnings and 
alarms. The units are the same as the output value scale. 
4.1.8.6. Min Out
Min Out is a minimum peak indicator for the AIFB output values.
4.1.8.7. Max Out
Max Out is a maximum peak indicator for the AIFB output values.
4.1.9.  Fail-safe Mode (PROFIBUS PA only)
4.1.9.1. Fail-safe Mode. 
Fail-safe Mode occurs if the status of the input value is bad, or if the device 
has been put into Fail-safe mode using Simulation. One of three options 
can be selected for the material level to be reported when the LOE timer 
expires.
4.1.9.2. Fail-safe Value 
(Accessible in PDM only after FS VALUE is selected in Fail-safe Mode).
User-defined default value for the OUT parameter, if sensor or sensor 
electronic fault is detected. Units are the same as the OUT value.
4.1.A. Human Interface
4.1.A.1. Decimal Point
The number of digits to display after the decimal point. (The LCD is limited 
to displaying three decimal places.)
Out unit text
If the code list does not contain a desired unit for the OUT parameter, (see 
General Requirement) you can write the specific text in this parameter. 
Handheld 
programmer 
Options
Material level to be reported
FS VALUE
Default value used as output value.
LAST VAL
* Store last valid output value.
USE BAD
Calculated output value is incorrect.
Values
Range: 
Default: 0.000