Siemens LR 460 User Manual

Page of 123
Page 62
SITRANS LR 460 – INSTRUCTION MANUAL
7ML19985JM01
mmmmm
Pa
ra
m
e
te
rs
4.1.1.  Target Mode (PROFIBUS PA only)
Used to request an operating mode from the Function Block.
4.1.2. Unit
Engineering unit to be displayed with the output value.
4.1.3.  Filter Time Constant
The time constant for the damping filter. The engineering unit is always in 
seconds. (This is an exponential filter: when a change occurs at the input, the 
output will be at 63.2% of the change in one time constant, and will be at full 
change after 5 time constants.)
4.1.4. Function
Used to select between the different level block outputs: Level, or Distance. (See 
 
on page 100 for an illustration.)
4.1.5.  Batch Information (PROFIBUS PA only)
These 4 parameters are intended to be used in Batch Applications conforming to 
IEC 61512 Part 1 (ISA S88). Other applications do not require these values, which 
are only stored in the Function Block.
4.1.5.1. Batch ID. 
Identifies a certain batch to allow assignment of equipment-
related information (for example faults, alarms) to the batch.
4.1.5.2. Batch Unit
Identifies the active Control Recipe Unit Procedure or the related Unit (for 
example, reactor, centrifuge, drier).
4.1.5.3. Batch operation
Identifies the active Control Recipe Operation.
4.1.5.4. Batch Phase
Identifies the active Control Recipe Phase.
Values
128
Out of Service (O/S)
16
Manual Mode (MAN)
8
*
Automatic Mode (AUTO) 
Options
percent
user--defined 
linear 
%
text
m, cm, mm, ft, in
default: m
Options
PV/Primary Value
Level 
SV1/Secondary Value 1
Level
SV2/ Secondary Value 2
Distance (value in sensor units)