SITRANS LR 460 – INSTRUCTION MANUAL 
Page 29
mmmmm
Quic
k
 S
tart
Operation types
1.4. Units
Select the units for the Quick Start variables (high and low calibration point, and level, 
distance, or space).
1.5. High Calibration Point
Distance from Sensor Reference to High Calibration Point: usually process full level. 
(See 1.3. Operation for an illustration.)
1.6. Low Calibration Point
Distance from Sensor Reference to Low Calibration Point: usually process empty 
level. (See 1.3. Operation for an illustration.)
1.7. Rate
Sets the reaction speed of the device to measurement changes in the target range.
Use a setting just faster than the maximum filling or emptying rate (whichever is 
greater). Slower settings provide higher accuracy: faster settings allow for more level 
fluctuation
1.8. Apply Changes
In order to save the Quick Start settings it is necessary to enable Apply Changes.
Select YES. SITRANS LR 460 is now ready to operate and returns to RUN mode.
Options
mm, cm, m, in, ft
Values
Range
 0.0000 to 100.00 m
Values
Range: 0.0000 to 100.00 m
Options
SLOW
0.1 m/minute
MED
1.0 m/minute
FAST
10.0m/minute
Options
YES, NO
SITRAN
S LR 40
0
high 
calibration 
point
low calibration point
level
space
distance
sensor reference point 
(flange face)