Siemens LR 460 User Manual

Page of 123
Page 28
SITRANS LR 460 – INSTRUCTION MANUAL 
7ML19985JM01
m
mmmm
Qui
c
k S
tart
Quick Start Wizard via the handheld programmer
The Quick Start menu appears as soon as you activate PROGRAM mode. 
1. Quick Start
a. Point the programmer at the display (from a maximum distance of 600 mm [2 ft.]), 
then press Mode  
to 
activate 
PROGRAM mode and open Menu level 1. 
b. Press Right ARROW 
 to navigate to menu item 1.1. 
c. Press Right ARROW  
to 
open 
Edit mode: the PROGRAM icon   will flash.
d. To change a setting, scroll to the desired selection or key in a new value.
e. After modifying a value, press Right ARROW 
 to accept it. The LCD displays 
the next menu item, the PROGRAM icon disappears, and the rightmost digit 
flashes to indicate Navigation Mode.
1.1. Language
1.2. Application Type
1.3. Operation
Notes: 
• The wizard is a complete package and the settings are inter-related.
• Do not use the Quick Start wizard to modify individual parameters: see instead 
• Changes apply only at the end of the sequence, after you select Apply changes. 
Note: 
There is no need to perform a Reset before starting the Quick Start sequence.
Options
ENGLISH, DEUTSCH, FRANCAIS, ESPANOL
Options
STEEL
Silo construction
CONCRETE
Options
LEVEL
Distance to material surface referenced from Low Calibration 
Point (process empty level).
SPACE
Distance to High Calibration Point (process full level) 
referenced from material surface.
DISTANCE
Distance to material surface referenced from Sensor 
Reference Point.