Connecting PROFIBUS PA
Typical PLC/mA configuration with PROFIBUS PA
(Continued from 
3.
Connect the earth conductor of the power supply to the earth terminal 
 on the 
metal bracket inside the enclosure. Adjust the cable length so that the earth 
conductor would be last to disconnect if cable is pulled.
4.
Tighten the cable gland and check the strain relief (pull and turn).
5.
Replace the enclosure cover and hand tighten it. The sealing ring must be clean and 
undamaged.
6.
Tighten the screw on the cover lock.
7.
Connect the external earth terminal located 
between the cable glands to a ground 
connection at your vessel. Use a cable with 
a cross-section of 2.5 mm
2
 or greater.