6  Troubleshooting
Issue A1
MICROMASTER 410    Operating Instructions
60
6SE6400-5EA00-0BP0
6.4 Alarms
Alarm
Possible Causes
Diagnose & Remedy
Reac-
tion
A0501
Current Limit
Ø  Motor power does not
correspond to the inverter power
Ø  Motor leads are too long
Ø Earth 
faults
Check the following:
1. 
Motor power (P0307) must correspond to
inverter power (r0206).
2. 
Cable length limits must not be exceeded.
3. 
Motor cable and motor must have no short-
circuits or earth faults
4. 
Motor parameters must match the motor in
use
5. 
Motor must not be obstructed or overloaded
Ø Increase 
the 
ramp-up-time.
Ø  Reduce the boost.
--
A0502
Overvoltage
limit
Ø  Overvoltage limit is reached.
Ø  This warning can occur during
ramp down, if the dc-link con-
troller is disabled (P1240 = 0).
If this warning is displayed permanently, check
drive input voltage .
--
A0503
UnderVoltage
Limit
Main supply failed
Check main supply voltage (P0210).
--
A0504
Inverter Over
Temperature
Warning level of inverter heat-sink
temperature (P0614) is exceeded,
resulting in pulse frequency reduction
and/or output frequency reduction
(depending on parametrization in
(P0610)
Check the following:
1. 
Ambient temperature must lie within
specified limits
2. 
Load conditions and duty cycle must be
appropriate
--
A0505
Inverter I
2
t
Warning level exceeded, current will
be reduced if parameterized
(P0610 = 1)
Check that duty cycle lies within specified limits
--
A0506
Inverter duty
cycle
Difference between heatsink and
IGBT junction temperature exceeds
warning limits
Check that duty cycle and shock loads lie within
specified limits
--
A0511
Motor Over
Temperature
I
2
t
Ø Motor 
overloaded.
Ø  Load duty cycle too high.
Check the following:
1. P0611 
(motor 
I
2
t time constant) should be
set to appropriate value
2. P0614 
(Motor 
I
2
t overload warning level)
should be set to suitable level
--
A0600
RTOS Overrun
Warning
Software problem
Contact Service Department
--
A0910
Vdc-max
controller de-
activated
Ø  Vdc max controller has been de-
activated
Ø  Occurs if main supply voltage is
permanently too high.
Ø  Occurs if motor is driven by an
active load, causing motor to go
into regenerative mode.
Ø  Occurs at very high load inertias,
when ramping down.
Check the following:
1. 
Input voltage must lie within range.
2. 
Load must be matched.
3. 
In certain cases apply braking resistor.
--
A0911
Vdc-max
controller
active
Vdc max controller is active; so ramp-
down times will be increased
automatically to keep DC-link voltage
(r0026) within limits
Check the inverter input voltage (P0210)
--