Honeywell 301C User Manual

Page of 107
Honeywell 301C User Manual 
The tables on pages 74-96 are also available on the Honeywell 
Analytics’ Commercial Products CD that accompanied the 301C 
Controller and from the Honeywell Analytics technical library  
(www.honeywellanalytics.com > Products > Commercial Solutions > 
301C > Technical Library
). 
Device Objects 
 
 
75 
 
Data Type
Required
1
Storage 
Type
2
BACnet 
Writeable?
Value
object_identifier
unsigned
R
N
N
Set from LUI
object_type
enumerated
R
C
N
device (8)
vendor_identifier
enumerated
R
C
N
Honeywell Inc. (17)
apdu_timeout
unsigned
R
C
N
0
application_software_version
character string
R
C
N
"1.1"
firmware_revision
character string
R
C
N
"1.3.18"
max_apdu_length_accepted
unsigned
R
C
N
1476
model_name
character string
R
C
N
"301C-BIP"
number_of_apdu_retries
unsigned
R
C
N
0
object_name
character string
R
N
N
default "VA301C:1", settable from LUI.
protocol_object_types_supported bit string
R
C
N
analog_input,
analog_output,
analog_value,
binary_input,
binary_value,
device
protocol_services_supported
bit string
R
C
N
readProperty,
readPropertyMultiple,
writeProperty,
deviceCommunicationControl,
reinitializeDevice,
i_Am,
i_Have,
timeSynchronization,
who_Has,
who_Is,
protocol_version
unsigned
R
C
N
1
segmentation_supported
enumerated
R
C
N
no_segmentation (3)
system_status
enumerated
R
C
N
operational (0)
vendor_name
character string
R
C
N
Honeywell
protocol_revision
unsigned
R
C
N
2
database_revision
unsigned
R
C
N
not meaningful
Notes
1  --  'R' indicates that this property is required by ASHRAE Standard 135
'O' indicates that the property is optional in ASHRAE Standard 135
2 --  'C' indicates the property is hard-coded as a constant
'N' indicates the property is stored in non-volatile memory
'R' indicate the property is computed constantly and stored in RAM.
Group
Property
De
vi
ce