3 INSTALLATION
NOTE !
Strictly observe the ‘UPS Safety Rules’.
Read carefully the UPS ‘Operating Manual & Installation
Guide’ before installing or operating the equipment.
Guide’ before installing or operating the equipment.
If any problems are encountered with the installation
procedure here described, please contact the nearest
procedure here described, please contact the nearest
Service Centre before proceeding.
3.1 3-PH SNMP/WEB PLUG-IN ADAPTER (P/N 1018959)
NOTE !
SitePro customers only
SitePro units produced before 2003 require an additional
protective ground connection – refer to APPENDIX A.
3.1.1 Setting the logical address
The logical address is configured through dip-switch SW1 in the following way:
Logical Address
Dip 1
Dip 2
SNMP Card 0
(1)
84
(54h)
ON
ON
SNMP Card 1
85
(55h)
ON
OFF
SNMP Card 2
86
(56h)
OFF
ON
SNMP Card 3
87
(57h)
OFF
OFF
(1) Default setup
Dip-switch SW1
NOTE: The logical address is a critical setting when more than one SNMP Card is installed in the same
UPS system.
Modifications reserved
Page 14/24
ISG_CNT_SNM_BAS_CRD_1GB_V012.doc
Installation Guide SNMP/Web Adapter