Schneider Electric DuraDrive Direct Coupled Actuators MA4X-707X User Manual
F-26642-8
© Copyright 2010 Schneider Electric All Rights Reserved.
7
INSTALLATION
Inspection
Inspect the package for damage. If damaged, notify the appropriate carrier immediately. If
undamaged, open the package and inspect the device for obvious damage. Return
damaged products.
undamaged, open the package and inspect the device for obvious damage. Return
damaged products.
Requirements
•
Job wiring diagrams
•
Tools (not provided):
– #8 sheet metal screws
– 10mm open end wrench or socket wrench
– 7/16 inch, open end wrench or socket wrench
– 1/8 inch, allen wrench
– Appropriate screwdriver(s)
– 10mm open end wrench or socket wrench
– 7/16 inch, open end wrench or socket wrench
– 1/8 inch, allen wrench
– Appropriate screwdriver(s)
•
Appropriate accessories
•
Training: Installer must be a qualified, experienced technician
MA40-7040
MA40-7041
MA40-7041
MA40-7040-501
MA40-7041-501
MA40-7041-501
120 Vac or
230 Vac
Wire No. 1
Wire No. 2
Neutral
Hot
2
2
Wire No. 2
Wire No. 1 Neutral
Hot
L1 N
L2 H
L2 H
L1 N
L2 H
1
1
3
Orange
Violet
Yellow
N.C.
COM.
N.O.
Auxiliary Switch 1
1 Provide overload protection and disconnect as
required.
2 Actuators may be wired in parallel. Power
consumption must be observed.
3 For end position indication, interlock control, fan
startup, etc., MA40-704X-501 model incorporates
one built-in auxiliary switch. See Specifications
section for details.
one built-in auxiliary switch. See Specifications
section for details.
120 Vac or
230 Vac
Green/Yellow
Green/Yellow
Voltage
Wire 1
Wire 2
120 Vac
White
Black
230 Vac
Light Blue
Brown
0 to 1 Scale
Adjustable
Figure-2 Typical Wiring Diagram for 120 Vac or 230 Vac Basic and Single Auxiliary Switch Models.
MA40-7043
MA40-7043-501
24 Vac
2
2
Red
Black
Common
Hot
1
1
(1)
(2)
3
Orange
Violet
Yellow
N.C.
N.O.
Auxiliary Switch 1
Line
Volts
1 Provide overload protection and disconnect as
required.
2 Actuators may be wired in parallel. Power
consumption must be observed. Actuator may also
be powered by 24 Vdc.
be powered by 24 Vdc.
3 For end position indication, interlock control, fan
startup, etc., MA40-7043-501 model incorporates
one built-in auxiliary switch. See Specifications
section for details.
one built-in auxiliary switch. See Specifications
section for details.
24 Vac
Black
Red
Common
Hot
Line
Volts
SPST Control Contact
SPST Control Contact
Green/Yellow
Green/Yellow
0 to 1 Scale
Adjustable
Figure-3 Typical Wiring Diagram for 24 Vac Basic and Single Auxiliary Switch Models.