Schneider Electric DuraDrive Direct Coupled Actuators MA4X-707X User Manual

Page of 24
F-26642-8
© Copyright 2010 Schneider Electric All Rights Reserved.
7
INSTALLATION
Inspection
Inspect the package for damage. If damaged, notify the appropriate carrier immediately. If 
undamaged, open the package and inspect the device for obvious damage. Return 
damaged products.
Requirements
Job wiring diagrams
Tools (not provided):
– #8 sheet metal screws 
– 10mm open end wrench or socket wrench
– 7/16 inch, open end wrench or socket wrench
– 1/8 inch, allen wrench
– Appropriate screwdriver(s)
Appropriate accessories
Training: Installer must be a qualified, experienced technician
MA40-7040
MA40-7041
MA40-7040-501
MA40-7041-501
120 Vac or
 230 Vac
Wire No. 1         
Wire No. 2         
Neutral
Hot
2
2
Wire No. 2         
Wire No. 1         Neutral
Hot
L1  N
L2  H
L1  N
L2  H
1
1
3
Orange       
Violet       
Yellow        
N.C. 
COM.
N.O.
Auxiliary Switch 1
1   Provide overload protection and disconnect as 
required.
2   Actuators may be wired in parallel. Power 
consumption must be observed.
3   For end position indication, interlock control, fan 
startup, etc., MA40-704X-501 model incorporates 
one built-in auxiliary switch. See Specifications 
section for details.
120 Vac or
 230 Vac
Green/Yellow
Green/Yellow
Voltage
Wire 1
Wire 2
120 Vac
White
Black
230 Vac
Light Blue
Brown
0 to 1 Scale
Adjustable
Figure-2 Typical Wiring Diagram for 120 Vac or 230 Vac Basic and Single Auxiliary Switch Models.
MA40-7043
MA40-7043-501
24 Vac
2
2
Red         
Black         
Common
Hot
1
1
(1)
(2)
3
Orange       
Violet       
Yellow       
N.C. 
N.O.
Auxiliary Switch 1
Line
Volts
1   Provide overload protection and disconnect as 
required.
2   Actuators may be wired in parallel. Power 
consumption must be observed. Actuator may also 
be powered by 24 Vdc.
3   For end position indication, interlock control, fan 
startup, etc., MA40-7043-501 model incorporates 
one built-in auxiliary switch. See Specifications 
section for details.
24 Vac
Black         
Red         
Common
Hot
Line
Volts
SPST Control Contact
SPST Control Contact
Green/Yellow
Green/Yellow
0 to 1 Scale
Adjustable