Schneider Electric DuraDrive Direct Coupled Actuators MA4X-707X User Manual

Page of 24
18
© Copyright 2010 Schneider Electric All Rights Reserved.
F-26642-8
Wiring Requirements
Control and Power Leads
See Table-3 for power wiring data. Refer to Figure-1 through Figure-3 for typical wiring 
applications.
Note: Class 2 control and power lead wiring must be routed separately from line voltage 
wiring and any other non-class 2 circuits. Line voltage, auxiliary switch, and auxiliary switch 
leads must be connected to a class 1 circuit.
Table-3 Power Wiring Data.
SIEBE
MA-7501-502
AM-673
Figure-4 Mounting Multiple Actuators.
Actuator Voltage
Part Number
Maximum Wire Run in ft. (m) (5% Voltage Drop)
14 AWG
16 AWG
18 AWG
24 Vac
22-30 Vdc
MA4X-7153
330 (101)
200 (61)
130 (40)
MA4X-7153-502
24 Vac
22-30 Vdc
MA40-7043
1100 (335)
700 (213)
440 (134)
MA40-7043-501
24 Vac
22-30 Vdc
MA4X-7073
600 (183)
500 (152)
254 (77)
MA4X-7073-502