5 Performance Data
B3L−19
CP 343-1 Lean for Industrial Ethernet / Manual Part B3L
Release 03/2007
C79000-G8976-C198-04
5.4
Characteristic Data for PROFINET IO
CP as PROFINET IO device
The CP supports the following maximum configuration as a PROFINET IO device:
Table 5-5
 
Characteristic
Explanation / Values
Size of the input area of the PROFINET IO device
512 bytes max.
Size of the output area of the PROFINET IO device
512 bytes max.
Size of the IO data area per submodule in a PROFINET IO device
S
Inputs
S
Outputs
240 bytes
240 bytes
Size of the consistency area for a submodule
240 bytes
Maximum number of submodules
32
Execution times of the FCs PNIO_SEND / PNIO_RECV
The calculation of the reaction times with PROFINET IO is determined by the
execution time of the function blocks required on the S7-300 CPU (PNIO_SEND,
PNIO_RECV).
Table 5-6
 
Component
Explanation / Values
Execution time on the CPU
315−2DP
(6ES7 315−2EG10−0AB0)
per PNIO_SEND block call:
S
< 1 ms at 240 bytes
per PNIO_RECV block call:
S
< 1 ms at 240 bytes
Execution time on the CPU
317−2PN/DP
(6ES7 317−2EJ10−0AB0)
per PNIO_SEND block call:
S
< 0.8 ms at 240 bytes
per PNIO_RECV block call:
S
< 0.8 ms at 240 bytes