Honeywell envirazone panel w8835 User Manual

Page of 32
W8835 ENVIRAZONE PANEL
9
68-0258—04
COM LED Operation
The green COM LED flickers as the W8835 communicates 
with the other EnviraCom devices: 
LED blinks rapidly—indicates device is currently 
transmitting information on the communications bus.
LED blinks once—indicates device received and 
acknowledged a message.
LED on constantly— indicates panel failure. Replace panel.
LED off constantly—indicates a wiring problem.
Table 3. LED Indicators
b
b
An LED change precedes the corresponding relay change by as much as six seconds.
Purge Mode
At the end of every call for heat or cool, the panel enters a 
Purge mode. DIP 4 configures the panel to purge for two 
(default) or three and one-half minutes. DIP switch 5 
configures the panel or the HVAC equipment to operate the fan 
during purge.
The Purge LED lights to signal that the system is in the Purge 
mode. Pressing the purge override button overrides the Purge 
mode.
Unless there is a new call for heat or cool during the Purge 
mode, all dampers are moved to the Open position at the end 
of purge. DIP switch 6 is used if it desired to open all dampers 
during the Purge mode.
Table 4.  Purge Configuration 
Table 5. Fan Control Configuration
Table 6.  Purge Damper Configuration
Individual Zone Fan Control
When all zones are satisfied, the fan switch of each thermostat 
controls the fan operation for that zone. When the fan setting is 
“ On”, the fan is energized, the fan LED illuminates and the 
dampers close to zones where the fan setting is “Auto”. If there 
is a call for heat or cool during this time, the fan mode ceases, 
and the heat or cool call is honored. When the zone calling is 
satisfied, and Purge mode has ended, the fan call resumes.
Single and Multi-Stage Conventional 
Heat Operation
The panel can control up to three stages of heating and two 
stages of cooling based on thermostat demand. Set DIP 
switches 1 and 2 for 1, 2 or 3 stages of heat. Set DIP switch 7 
for one or two stages of cooling.
Table 7. Conventional Equipment Configuration
LED
Color
Illuminated
Not Illuminated
Heat
Red
Heat call.
No heat calls.
Cool
Green
Cool call.
No cool calls.
Purge
Amber
Purge mode.
Not in Purge mode.
Fan
Green
Fan only call.
No fan only call.
Em Heat
Red
Emergency Heat mode.
Not in Emergency Heat mode.
Zone 1, 2, 3
Green
Damper is open or opening.
Damper is closed or closing.
DIP Switch 
Number
Status
Purge
4
Off (Down)
3.5 minutes purge
4
On (Up)
2 minutes purge
DIP Switch 
Number
Status
Fan Control
5
Off (Down)
Panel control of fan 
in Purge
5
On (Up)
HVAC control of fan 
in Purge
DIP Switch 
Number
Status
Purge Damper
6
On (Up)
Last zone(s) calling 
open during Purge
6
Off (Down)
Open all dampers 
during Purge
1 Stage Cooling
Equipment Type
DIP 1
DIP 2
1 Stage Conventional
On (Up)
On (Up)
2 Stage Conventional
On (Up)
Off (Down)
3 Stage Conventional
Off (Down)
On (Up)
2 Stage Cooling
Cooling Stage
DIP7
1 Stage
On (Up)
2 Stage 
Off (Down)