Honeywell envirazone panel w8835 User Manual

Page of 32
W8835 ENVIRAZONE PANEL
68-0258—04
4
Table 2. Required Accessories (Not Supplied with Panel).
a
Supplied in the Y8835 kits.
INSTALLATION
Mounting
CAUTION
Equipment Damage Hazard.
Do not mount W8835 inside HVAC equipment.
Mount only on wall or on cold air return.
1. Mount the thermostats in each zone of the living space 
using the installation instructions provided with each 
thermostat.
2. Mount the dampers in the ductwork using the installation 
instructions provided with each damper.
3. Mount the W8835 EnviraZone Panel near the HVAC 
equipment; locate it on a wall or on the cold-air return. 
See Fig. 2.
4. Level the W8835 for appearance only.
Fig. 2. W8835 mounting location.
Wiring
CAUTION
Voltage Hazard.
Can cause electrical shock or equipment damage.
Disconnect power before continuing installation.
Wiring must comply with applicable codes, ordinances,
and regulations.
Accessory
Description
Bypass Rating
(cfm)
40 VA transformers 
AT140A1042
a
High and low limit sensor
C7835A1009
a
Round static pressure regulator damper
SPRD7
SPRD8
SPRD9
SPRD10
SPRD12
SPRD14
SPRD16
300 
400 
600 
750 
1200 
1800 
2400 
Rectangular static pressure regulator damper
SPRD12x8
SPRD12x10
SPRD12x12
SPRD20x8
SPRD20x10
SPRD20x12
1000 
1200 
1400 
1600 
2000 
3000 
M31121
W8835 
ELE
CTRONI
C AIR 
CLEANER 
RETURN 
AIR 
W8835 
FURNACE
AIR CLEANER