LG gj176p User Manual
SPECIFICATIONS for LG HERMETIC COMPRESSOR
LG
R410A
Standard Dimensions
90
。
120
。
Φ
176
3 - Φ19.1
S
R
C
DIS. I.D 9.7
±
0.15
42
Φ
127.7
+
0.15
0
SUC. I.D 12.8
Φ
75
266.2
2.3
37
.2
113
±
3
251.6
293.6
33
20
22
9
±
3
±
3
Detail of ⓐ
Detail of ⓑ
10
.0
0.5
10
.0
0.5
G J 1 7 6 P
1PH, 220/240V
– 50Hz
Application Range
Compressor Cooling Natural
Eva. Temp. Range -10℃ ~ 12℃
Eva. Temp. Range -10℃ ~ 12℃
14℉ ~ 54℉
Condensing Temp.
65℃ max.
149℉ max.
Return Gas Temp. 35℃ max.
95℉ max.
Discharge gas Temp. 115℃ max.
239℉ max.
Motor Wire Temp. 130℃ max.
266℉ max.
Rated Performance
Capacity
14,400/14,550 Btu/h
4,220/4,264 Watts
Motor Input 1,485/1,532 W
Current Not Fixed
EER 9.7/9.5 Btu/W.h
Current Not Fixed
EER 9.7/9.5 Btu/W.h
2.84/2.78 W/W
Compressor Data
Design Rolling Piston Typed Rotary
Displacement 17.6 cc/rev
Displacement 17.6 cc/rev
1.07 in
3
/rev
Oil / Oil Charge FVC 68D (PVE) / 440 cc
Weight
Weight
14.7 Kg 32.3 lb
Motor Data
Motor Type 2 Pole Induction (PSC)
Voltage Range 198 V to 264 V
Locked Rotor Amps. Not Fixed
Voltage Range 198 V to 264 V
Locked Rotor Amps. Not Fixed
Electrical Components
Comp. Tri-plate
Bolt, Stud
Nut, Hexagon
Grommet
Unit Base
Washer, Plain
28 m
m
(1
.10 in
ch
)
Compressor Mounting
Wiring Diagram
※
C.S.R mark is embossed on a Cover Terminal
Line
Running Capacitor
Compressor
C
S
R
O.L.P
Running Capacitor 40 ㎌
400 VAC (Not Fixed)
Overload Protector Internal Type (Not Fixed)
Capacity Test Conditions
Evaporating Temp.
7.2℃
45℉
Condensing Temp. 54.4℃
130℉
Return Gas Temp. 35.0℃
95℉
Liquid
Temp. 46.1℃
115℉
Ambient Temp. 35.0℃
95℉
Specifications are subject to change without notice.
Normal Performance value ±5%.
Normal Performance value ±5%.
Air Conditioning Compressor Division