Toshiba lf516 User Manual

Page of 157
 
 
 130 − 
 
6 F 8 A 0 9 3 4  
Note1 : Even if the custom unit is selected, the current output does not change unless the 
span value is changed. 
Display example 
Description 
R1 
 
   2.00000 
 
     
m
3
/min 
 
 
 
In the case of span value = 2.00000 m
3
/min
 
 
R1 
 
   20000.0 
 
    
*dL/min
 
 
 
 
When custom unit dL/min is selected, the span value is   
displayed 20000 automatically based on the custom   
coefficient. 
 
Identification character “*” showing the custom unit is 
displayed at the head of custom unit. 
 
Even if setting is fixed in this state, the current output 
does not change.
 
R1 
 
   
1
0000.0 
 
    *dL/min 
 
 
 
When the span value was changed after the custom   
unit selection, the current output changes. 
 
The span value is changed into 10000 from 20000 in   
display example. The percent value doubles when   
setting is fixed in this state, and the current output   
changes. 
 
Note2 : Setting range of the span value depends on the custom coefficient. 
              If the setting high limit of the span value is 1.18 m
3
/min
the setting high limit is 11800 dL/min by the custom unit. 
 
Note3 : In the case of the multiple ranges, the custom unit is applied to Range4 from Range2.