Switch operation 
Display example 
Description 
STEP1 
 
 
 
ALM 4-20 
 
UNDER 3mA 
 
 
 
 
 
The currently set value (UNDER 3.0mA in 
this example) appears. 
 
Then push              . 
 
* Pushing       returns you to the setting 
menu. 
STEP2 
 
 
 
ALM 4-20 
 
UNDER 3mA
 
 
        
 
 
The switches at the bottom change. 
(                                        are shown.) 
At the same time, the cursor appears. 
(The item indicated by the cursor is 
highlighted.) 
 
Then push                          . 
STEP3 
 
 
 
ALM 4-20 
 
4mA
 
 
        
 
 
You can continue to change the setting item.
Push                          to  change  the  selection 
items. 
: Selected item is scrolled up. 
: Selected item is scrolled down. 
When the desired item is selected, push         
    to set the item temporarily. 
STEP4(=END) 
 
 
 
ALM 4-20 
 
4mA 
 
        
SET OK?
 
 
 
When you push       , a message appears 
to confirm whether the setting is OK or not. 
If OK, push       . If you want to redo the 
setting, push       . 
 
Pushing      cancels the setting operation 
and exits the setting screen. 
 
 
8.2.17 Output Low Limit Setting 
 
The low limit of the current output for converter can be set. 
The output low limit can be selected from the items listed in the table below. 
 
● Output low limit setting function 
Selection items
Output low limit 
  4.0mA 
The current value can be outputted up to 4.0mA (0%). 
  3.2mA 
The current value can be outputted up to 3.2mA (
−5%). 
  2.4mA 
The current value can be outputted up to 2.4mA (
−10%). 
Note: If the low cutoff value in 8.2.12 “Low Cutoff” is set to a value other than 0%, the output low 
limit value will be fixed to 4.0mA, regardless of the set value. 
 