Toshiba lf546 User Manual
−
55 −
6 F 8 A 0 9 3 4
8.2.2 Exciting Current Value
The exciting current value can be checked/changed by the following procedures.
Be sure to match the exciting current value with the value specified for the
combined detector.
Specifying any other value may cause an error.
combined detector.
Specifying any other value may cause an error.
Shown below is an example of changing the exciting current value from 0.1900A to 0.2150A.
Switch operation
Display example
Description
A:DETECTOR
1 EXC CUR
2 SIZE
3 EXC FREQ
4 FLOW DIR
5 EXIT
Select "EX CUR" from the setting item
selection menu.
selection menu.
STEP1
EXC CUR
0.1900
A
The currently set excitation current value
(0.1900A in this example) appears.
Then push .
* Pushing returns you to the setting
(0.1900A in this example) appears.
Then push .
* Pushing returns you to the setting
menu.
STEP2
EXC CUR
0
.1900
A
The switches at the bottom change.
( are shown.)
At the same time, the cursor appears.
(The digit indicated by the cursor is
highlighted.)
Then push .
( are shown.)
At the same time, the cursor appears.
(The digit indicated by the cursor is
highlighted.)
Then push .
STEP3
EXC CUR
0.
1
900
A
You can continue to change the setting
value. Push to move the cursor to
the digit you want to change. (You can hold
down the switch longer for continuous
operation.)
Then push .
value. Push to move the cursor to
the digit you want to change. (You can hold
down the switch longer for continuous
operation.)
Then push .
STEP4
EXC CUR
0.
2
900
A
You can continue to change the setting
value. Pushing increments the
number of the digit the cursor is positioned.
(You can hold down the switch longer for
continuous operation.)
value. Pushing increments the
number of the digit the cursor is positioned.
(You can hold down the switch longer for
continuous operation.)
STEP5
EXC CUR
0.2150
A
Repeat this operation to change the value to
0.2150A
0.2150A
.
When the desired value is obtained, push
to set the value temporarily.
ESC
ESC
ESC