Toshiba 1000 User Manual

Page of 64
 
 
 
18 
6.  Computer and Alarm Connections 
At the rear of the UPS is an interface that allows direct communication with a computer 
system  (see  Figure 2, Pg. 14). There is a RS232 serial data interface, a  USB data 
interface, and an emergency power off switch. The RS232 port and the USB interface 
cannot be used simultaneously. 
In addition there is an optional interface slot that allows for the installation of 
communications cards. It may be used in parallel with either the RS232 or USB ports. 
An SNMP/WEB card  is available for the optional interface slot that allows for the 
RemotEye II to manage and monitor the system over a network or over the internet. 
6.1 
RS-232 Standard Interface Port 
Only the communication cable provided with the UPS may be used to connect the UPS 
to a computer when using the RS232 port of the UPS. Ensure that the operating system 
of the computer supports RS232 communications.  Other advanced power protection 
solutions, such as SNMP, are available from your dealer. 
The RS-232 interface uses a 9-pin D-sub connector. The names and functions of the port 
pins are listed in the following table.  
 
Pin # 
Signal 
Direction (re UPS) 
Functions 
TxD 
Output 
TxD Output 
RxD 
Input 
RxD / Inverter Off Input 
Common 
 
Common 
 
Output (Normally Open)  AC Fail (13VDC) 
 
Output (Normally Open)  Low Battery (13VDC) 
 
Output 
8–24 VDC Power 
Note:  In Battery mode, the UPS will be turned off 2 minutes after 5V is applied to Pin 3 and Pin 5 for more 
than 5seconds. 
Table 1 : RS232 Pin Out Signal 
DB9 Female Connector Outline 
(facing connector)