Honeywell Liquid Cooled 25kW Home Standby Generator Owner's Manual
SPECIFICATIONS
STATIONARY EMERGENCY GENERATOR
Type......................................................................Synchronous
Rotor Insulation .............................................................Class H
Stator Insulation ............................................................Class H
Telephone Interference Factor (TIF) .................................. < 50
Alternator Output Leads 3-phase ..................................... 4-wire
Bearings ..................................................................Sealed Ball
Coupling ................................................................Flexible Disc
Load Capacity (Standby Rating) .....................................25kW*
*
NOTE: Generator rating and performance in accordance with ISO8528-5, BS5514, SAE
J1349, ISO3046 and DIN 6271 Standards. KW rating is based on LPG fuel and may derate
with natural gas and generator specific settings.
with natural gas and generator specific settings.
Excitation System ............................................................Direct
Generator Output Voltage/kW - 60 Hz kW
Amp CB Size
120/240V, 1-phase, 1.0 pf
25
104
125
120/208V, 3-phase, 0.8 pf
25
87
100
120/240V, 3-phase, 0.8 pf
25
75
90
Generator Locked Rotor KVA Available @ Voltage Dip of 35%
25kW
25kW
42 KVA
ENGINE
Make ........................................................................... Generac
Model ......................................................................... In Line 4
Cylinders and Arrangement .....................................................4
Displacement ............................................................... 2.4 Liter
Bore............................................................ 86.5 mm (3.41 in.)
Stroke .......................................................... 100 mm (3.94 in.)
Compression Ratio....................................................... 9.5-to-1
Air Intake System ......................................... Naturally Aspirated
Valve Seats ................................................................ Hardened
Lifter Type .................................................................. Hydraulic
Spark Plug Gap ...................1.07 - 1.17mm (0.042 - 0.46 inch)
Engine Parameters
Rated Synchronous RPM .......................................60 Hz, 1800
Exhaust System
Exhaust Flow at Rated Output 60 Hz (22/27kW) ....165/180 cfm
Exhaust Temp. at Rated Output (22/27kW) ........... 900°/1000° F
Combustion Air Requirements (Natural Gas)
Flow at rated power, 60 Hz .............................................68 cfm
Governor
Type...........................................................................Electronic
Frequency Regulation .............................................Isochronous
Steady State Regulation ..............................................± 0.25%
Engine Lubrication System
Type of Oil Pump ...............................................................Gear
Oil Filter ......................................... Full Flow Spin-on, Cartridge
Crankcase Oil Capacity ....................................... 5.25 U.S. qts.
(including oil filter capacity)
COOLING SYSTEM
Type............................................. Pressurized Closed Recovery
Water Pump ............................................................. Belt Driven
Fan Speed ..................................................................1980 rpm
Fan Diameter ...........................................................18.1 inches
Fan Mode ....................................................................... Pusher
Air Flow (inlet air including alternator and
combustion air) ................................................. 2400 ft
3
/min.
Coolant Capacity ................................................. (3.0 U.S. gal.)
Heat Rejection to Coolant (25kW) .......................105,000 Btu/h
Maximum Operating Air Temp. on Radiator ......... 60° C (150° F)
Maximum Ambient Temperature ......................... 50° C (140° F)
FUEL SYSTEM
Type of Fuel ....................................Natural Gas, Propane Vapor
Carburetor............................................................... Down Draft
Secondary Fuel Regulator............................................ Standard
Fuel Shut-off Solenoid ................................................. Standard
Operating Fuel Pressure ................. 5 in. - 14 in. Water Column
Fuel Consumption - ft
3
/hr (Natural Gas/LPV)
Exercise 25% 50% 75% 100%
Cycle Load Load Load Load
25kW 42/16 108/43 197/78 287/114 359/143
ELECTRICAL SYSTEM
Battery Charge Alternator ......................................12V, 30 Amp
Static Battery Charger ..................................................2.5 Amp
Recommended Battery .................................Group 26, 525CCA
System Voltage ............................................................ 12 Volts
Voltage Regulator
Type...........................................................................Electronic
Sensing ................................................................ Single-phase
Regulation ........................................................................± 1%
Features ......................................... Adjustable Voltage and Gain
Power Adjustment for Ambient Conditions
Temperature Deration
3% for every 10° C above °C (25kW) ..................................25
1.65% for every 10° above °F (25kW) ..........................104/77
Altitude Deration
1% for every 100 m above m (25kW) ...............................183
3% for every 1000 ft. above ft. (25kW) ....................2500/600
Controller ................................................................. Nexus
Specifications
6-1
GenSpec092 Rev
. B 05/11