EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER
37
74-2958—1
Table 10. W7750A Version I/O Description.
IMPORTANT
If the W7750A controller is configured by E-Vision, 
the outputs may be assigned in different order than 
the factory defaults. Use the Custom Wiring function 
of E-Vision to re-assign the outputs to the desired 
terminals.
The W7750B,C Versions are preconfigured with the same 
factory default setup as the W7750A Model; however, some 
terminals for wiring connections differ on the W7750B,C 
Models. See Fig. 30 for the terminal names on the W7750B 
Model and Fig. 35 for the terminal names on the W7750C 
Model. The factory default configuration of the digital output 
points on the W7750B,C Models follow (terminal names are 
from the W7750A):
FACTORY DEFAULT DIGITAL OUTPUTS:
FREE 1 (OUT 1) DO1—NETWORK DO
(OUT 2) DO2—SUPPLY FAN START/STOP
(OUT 3) DO3—COOL_STAGE_2
(OUT 4) DO4—COOL_STAGE_1
(OUT 5) DO5—HEAT_STAGE_2
(OUT 6) DO6—HEAT_STAGE_1
DO7—UNUSED
DO8—UNUSED
The Wall Module terminals are identical for the W7750A,B,C 
Models.
The W7750B,C Models offers two voltage/current sensor 
input terminals. When current-type sensors (4 to 20 mA) are 
configured, the W7750B,C automatically switches a 249 ohm 
resistor into the sensing circuit; so no external resistor is 
required. The W7750A Model does not support voltage or 
current inputs.
NOTE:
If using factory defaults, DI-2 input is configured for 
ScheduleMaster (nvoIO.SchedMaster). For a 
stand-alone unit, either connect an external time 
clock to terminals 9 and 10 or put a jumper on 
terminals 9 and 10 (using a jumper puts the 
controller in continuous occupied mode).
Terminal
Terminal Number
Description
DO6–(W1)
31
Heat 1 (or Reversing Valve for a Heat Pump)
DO5–(W2)
30
Heat 2 (or Aux. Heat for a Heat Pump)
DO4–(Y1)
29
Cool 1 (or Compressor 1 for a Heat Pump)
DO3–(Y2)
28
Cool 2 (or Compressor 2 for a Heat Pump)
DO2–(G)
27
Fan
DO1–NET
26
Network Digital Output
DO1–NET
25
Network Digital Output (connect to terminal number 22 +24Vac)
Rc
24
Control power for relay contacts DO2 (G), DO3 (Y1) and DO4 (Y2) 
Rh
23
Control power for relay contacts DO5 (W1) and DO6 (W2)
+24Vac (H)
22
Power for the controller
COM (N)
21
Return for power to controller
E-Bus
14 and 15
Echelon communications (L
ON
W
ORKS
 Bus) screw terminals
DI - 2
12
Digital Input 2
DGND
11
Digital Ground
DGND
10
Digital Ground
DI - 1
9
Digital Input 1
AGND
8
Analog ground
AI - 1 OHM
7
Analog Input 1 (used for Discharge Air Temperature Sensor)
SET PT
6
Space temperature setpoint potentiometer
GROUND
5
Wall Module
SENSOR
4
Space temperature sensor
BYPASS
3
Space override button
LED
2
Space LED for indication of manual occupancy status
EARTH GND 1
Earth Ground