Schneider Electric EM4000 User Manual

Page of 44
930-134-01-A.00 
PowerLogic
TM
 Series EM4000
11/2013
Installation Guide
©2013 Schneider Electric All Rights Reserved
1
Introduction
This document describes the PowerLogic EM4033 and EM4080 meters, including 
procedures to install and start up the unit, and complete the initial configuration:
This documentation is intended for those responsible for installing and configuring 
the PowerLogic EM4033 and EM4080 meters. Installers must be qualified 
electricians with knowledge of local and national code requirements. See “Safety 
Precautions” on page 5.
System Description
The PowerLogic EM4033 and EM4080 meters support:
• single-phase, 2-wire
• single-phase, 3-wire (network)
• three-phase wye and Delta services 
Depending on how the meters are installed and configured, they can meter 8, 12, or 
24 individual meter points. The PowerLogic EM4033 and EM4080 meters are 
designed for residential, commercial, and industrial use and display the power and 
consumption readings for each measurement point. 
PowerLogic EM4000 series System Specifications
The PowerLogic EM4000 series system architecture includes:
• single-phase, 2-wire; single-phase, 3-wire (network); three-phase, 4-wire (wye); 
and three-phase, 3-wire (delta) compatibility
• 2 control voltage variants: 120V 60Hz and 277V 60Hz
• 120/208V, 120/240V and 277/480V configurations, and 347/600V with external 
potential transformers
• up to 8, 12, or 24 individual meter points
• local Ethernet configuration interface via PC and web browser
• Ethernet port for remote reporting
• Modbus RTU serial port, for remote reporting
• serial port for remote display
• 2 pulse inputs to connect metering devices 
Table 1 lists the system specifications of the PowerLogic EM4033 and EM4080 
meters.