User Interface for Setup
USER INTERFACE FOR SETUP
Next
Next
From:
 SETUP > PASWD
ADDR
--------
001
BAUD
--------
38400
19200
9600
4800
2400
1200
PAR
--------
nOnE
EvEn
Odd
Set Communications Parameters:
ADDR - Modbus Address: 1 – 247. 
Press + to increment the selected (blinking) digit.
Press - to select the digit to the left.
BAUD - Baud Rate: 1200 – 38400 Baud
PAR - Parity: Odd, Even, None
Press + or - to step through the options.
Set Current Transducer:
CT V - CT Input Voltage: + or – to Select 1.0 or 0.33V.
CT SZ - CT Size: in Amps. Maximum is 32000 Amps.
Set System Configuration: 
SYSTM:   + or – to step through the following System Type options:
System Reg 130 CTs Description
3L-1n
40
3        Wye Three Phase: A, B, & C with Neutral (Default).
3L
31
3        Delta Three Phase: A, B & C; no Neutral
2L-1n
12
2        Single Split Phase: A & B with Neutral
2L
11
1        Single Phase: A & B; no Neutral
1L-1n
10
1        Single Phase: A to Neutral
System 
Type
Current 
Transformer
S  SYS
Next
S  CT
CT V
--------
1.0
.33
CT SZ
--------
100
SYSTM
--------
3L-1n
  3L
  2L-1n
  2L
  1L-1n
Bac
To
 SETU
P
Back
Back
Back
S COM
To Setup p. 2 “SPLOS”
Next
S  PT
Set Potential Transfomer Ratio: 
RATIO – Potential transformer step down is RATIO:1. Default is 1:1 
(No PT installed). See Install for wiring diagrams. This value must be 
set before the System Voltage (if used).
Potential
Transformer
RATIO
--------
001.00
Back
S     V
Back
Sytem
Voltage
Next
Set System Voltage:
V LL – The nominal Line to Line Voltage for the system. This is used 
by the meter to calculate the theoretical maximum system power, and 
as the reference voltage for setting the Phase Loss threshold. 
Maximum is 32000 Volts. For system type 1+N (10), this is a Line to 
Neutral Voltage, indicated by “V LN”. Note: the meter will reject settings 
that are not within the meter’s operating range when divided by the PT 
ratio. 
  V LL
--------
00600
S  PWR
Back
Sytem
Voltage
MX  KW 
--------
103.92
Next
System Power:
MX KW – The theoretical Maximum System Power is calculated by the 
meter from the System Voltage, CT size, and System Type. Power 
Factor is assumed to be unity. The value of System Power is used to  
determine which combinations of pulse weight and duration are valid 
and will keep up with the maximum power the meter will see. This value 
is read only. 
Note: 
Bold is the Default.
To Setup p. 2 “SPASS”
RS-485
Output