Siemens 6ED1050-1AA00-0BE8 User Manual

Page of 372
 
Configuring LOGO! 
 
7.2 Setting the default values for LOGO! 
LOGO! 
Manual, 04/2011, A5E03556174-01 
299
 
7.2.4 
Setting the number of AIs in the LOGO! Basic 
LOGO! 12/24RC/RCo/RCE, LOGO! 24/24o and LOGO! 24C/24Co support up to four 
onboard inputs that can be used as either digital or analog inputs (0 ...10V). Inputs I7 (AI1) 
and I8 (AI2) are available as analog inputs by default, whether you use them or not. Inputs I1 
(AI3) and I2 (AI4) are optional analog inputs. A LOGO! Basic provides a menu where you 
can choose to use two analog inputs (the default, AI1 and AI2), or four. Regardless of the 
settings, inputs I1 and I2 can be used as digital inputs. To use them as analog inputs AI3 
and AI4, you must set the 'BM AI NUM' to four. Note that the number of configured analog 
inputs on the LOGO! Basic affects the subsequent numbering of analog inputs on attached 
expansion modules (See the "Maximum setup (Page 34)" topic). 
You can set the number of AIs in programming mode only. 
To set the number of AIs in programming mode: 
1.  In the main menu, select "
": Press   or   
6WDUW
!6HWXS
&DUG
3URJUDP
 
2.  Confirm "
": Press OK 
%0$,180
0HQX/DQJ
/&'
!&ORFN
 
3.  Select "
": Press   or   
4.  Confirm "
": Press OK 
5.  Move to "2AI" or "4AI": Press   or   
6.  Confirm selection: Press OK 
 
 
Note 
If you change the number of analog inputs, LOGO! restarts automatically. 
 