G8000 Series Installation and Operation Manual
10.3    Anchor Bolts
Install the anchor bolts to secure the UPS on the floor. See Figure 10.2 for anchor bolt installation detail.
Use 12mm (1/2”) diameter anchor bolts. There are 16mm (5/8”) diameter holes provided in the UPS base. 
See Figure 10.3 for the hole locations and dimensions for the specified UPS models.
4 x 5/16 in. (16 mm) 
diameter screw holes
4 screw holes 
(Side View)
Anchor Bolt
FIGURE 10.2
ANCHOR BOLT INSTALLATION DETAIL
FIGURE 10.3
HOLE LOCATIONS/DIMENSIONS 
ON BOTTOM OF UPS
Back
Front
4 x 0.5 in. - Dia. (12 mm)
29.7 in. (755 mm)
21.7 in.
(551 mm)
80/100/125 kVA 
(See Appendix B)
 
21.7 in.
(551 mm)
Back
Front
4 x 0.5 in. - Dia. (12 mm)
46.1 in. (1171 mm)
150/225 kVA
(See Appendix B)
25.6 in.
(650 mm)
Back
Front
8 x 0.5 in. - Dia. (12 mm)
22.5 in.
(571 mm)
300 kVA 
(See Appendix B)
22.5 in.
(571 mm)
22.5 in.
(571 mm)
500 kVA
(See Appendix B)
30.0 in.
(762 mm)
Back
Front
12 x 0.5 in. - Dia. (12 mm)
33.9 in.
(862 mm)
20.0 in.
(508 mm)
22.4 in.
(568 mm)
20.0 in.
(508 mm)
3.0 in. (76 mm)
Input Section
Output Section