6  Commissioning 
MICROMASTER 440   
Operating Instructions (Compact) 
75
 
6.5 Series 
commissioning 
An existing parameter set can be transferred to a MICROMASTER 440 frequency 
inverter using STARTER or DriveMonitor (refer to Section 4.1 "Establishing 
communications MICROMASTER 440 
⇔ STARTER"). 
Typical applications for series commissioning include: 
1.  If several drives are to be commissioned that have the same configuration and 
same functions. A quick / application commissioning (first commissioning) must 
be carried-out for the first drive. Its parameter values are then transferred to the 
other drives. 
2.  When replacing MICROMASTER 440 frequency inverters. 
 
6.6 
Parameter reset of factory setting 
 
 
 
 
User access level 
 1  Standard 
 
Parameter filter 
 0  All parameters
 
 
Commissioning parameter 
30 Factory 
setting 
 
Factory reset 
 0  disabled 
 1  Parameter reset 
 
 
The drive inverter carries-out a parameter reset (duration, approx. 10 s) and then 
automatically exits the reset menu and sets: 
 
P0970 = 0 : 
disabled 
 
P0010 = 0 : 
ready 
 
 
 
START
END
 
P0010 = 30 
 
P0970 = 1 
0
 
0
 
 
P0003 = 1 
 
P0004 = 0 
1
 
0