Siemens 440 User Manual

Page of 78
6  Commissioning 
Issue 10/06 
 
MICROMASTER 440 
72 
Operating Instructions (Compact) 
6.4.20 Diagnostic 
parameters 
 
r0021    CO: Act. filtered frequency 
Displays actual inverter output frequency (r0021) excluding slip compensation, resonance 
damping and frequency limitation. 
 
r0022    Act. filtered rotor speed 
Displays calculated rotor speed based on inverter output frequency [Hz] x 120 / number of 
poles. 
r0313
 
60
 
 
[Hz]
 
r0021
  
 
[1/min]
 
r0022
=
 
 
r0032    CO: Act. filtered power 
Displays motor power (power output at the motor shaft). 
Motor
ω, M
M
 
 
f
 
 
2
 
 
M
 
 
 
 
P
mech
π
=
ω
=
[Nm]
 
r0031
 
[1/min]
 
60
 
r0022
 
 
 
π
 
2
 
 
1000
 
1
 
 
[kW]
 
r0032
=
[kW]
 
r0032
 
 
0.75
 
 
[hp]
 
r0032
=
 
 
r0035    CO: Motor temperature 
Displays the measured motor temperature in °C.
 
 
r0036    CO: Frequency inverter utilization 
Displays the frequency inverter utilization as a % referred to the overload. In so doing, the 
value is calculated using the I
2
t model. 
The I
2
t actual value relative to the maximum possible I
2
t value provides the level of 
utilization.
 
 
r0039    CO: Energy consumpt. meter [kWh] 
Displays electrical energy used by inverter since display was last reset. 
ist
dt
cos
i
u
3
dt
P
r0039
0
0
W
ϕ
=
=
ist
t
t
 
 
r0052    CO/BO: Act. status word 1 
Displays the first active status word (ZSW) of the frequency inverter (bit format) and can be 
used to diagnose the inverter status. 
Bit00   Drive ready                                0  NO         1  YES 
Bit01   Drive ready to run                         0  NO         1  YES 
Bit02   Drive running                              0  NO         1  YES 
Bit03   Drive fault active                         0  NO         1  YES 
 
Bit04   OFF2 active                                0  YES        1  NO 
Bit05   OFF3 active                                0  YES        1  NO 
Bit06   ON inhibit active                          0  NO         1  YES 
Bit07   Drive warning active                       0  NO         1  YES 
 
Bit08   Deviation setpoint / act. value            0  YES        1  NO 
Bit09   PZD control                                0  NO         1  YES 
Bit10   Maximum frequency reached                  0  NO         1  YES 
Bit11   Warning: Motor current limit               0  YES        1  NO 
 
Bit12   Motor holding brake active                 0  NO         1  YES 
Bit13   Motor overload                             0  YES        1  NO 
Bit14   Motor runs right                           0  NO         1  YES 
Bit15   Inverter overload                          0  YES        1  NO