6  Commissioning 
Issue 10/06 
 
MICROMASTER 440 
32 
Operating Instructions (Compact) 
6.2 
Motor data identification 
 
 
 
Factory setting
 
Ambient motor temperature
 (entered in °C) 
The motor ambient temperature is entered at the instant that motor data is 
being determined (factory setting: 20 °C). 
 
 
 
yes no 
The difference between the motor temperature and the motor ambient 
temperature P0625 must lie in the tolerance range of approx. ± 5 °C. If this is 
not the case, then the motor data identification routine can only be carried-out 
after the motor has cooled down. 
 
 
 
 
 
Select motor data identification
 with P1910 = 1 
p1910 = 1:  Identifies the motor parameter with parameter change.  
These are accepted and applied to the controller.  
When  p1910 = 1 is selected, Alarm A0541 (motor data identification active) 
is output, and internally p0340 is set to 3. 
 
Starts the motor data identification run 
with p1910 = 1 
The measuring operation is initiated with the continuous (steady-state) ON 
command. The motor aligns itself and current flows through it. Diagnostics is 
possible using r0069 (CO: Phase current).  
 
After the motor data identification routine has been completed, p1910 is reset 
(p1910 = 0, motor data identification routine inhibited) and Alarm A0541 is 
cleared (deleted). 
 
In order to set the frequency converter into a defined state, an OFF1 command 
must be issued before the next step. 
 
Select motor data identification
 with P1910 = 3 
p1910 = 3: Identifies the saturation characteristic with parameter change. 
When p1910 = 3 is selected,  Alarm A0541 (motor data identification active) 
is output and internally, p0340 is set to 2. 
 
Starts the motor data identification run 
with P1910 = 3 
The measuring operation must be started with a continuous ON command. 
 
After the motor identification routine has been completed, p1910 is reset 
(p1910 = 0, motor data identification routine inhibited) and Alarm A0541 is 
cleared (deleted). 
 
In order to set the frequency converter into a defined state, an OFF1 command 
must be issued before the next step. 
 
 
 
6.3 Magnetizing 
current 
¾
  The value of the magnetizing current r0331/P0320 has a significant influence on 
the closed-loop control. This cannot be measured at standstill. This means that 
the value is estimated for standard 4-pole 1LA7 Siemens standard using the 
automatic parameterization P0340=1 (P0320=0; result in r0331). 
¾
  If the deviation of the magnetizing current is too high, then the values for the 
magnetizing reactance and those of the rotor resistance will not be able to be 
accurately determined. 
¾
 Especially for third-party motors it is important that the magnetizing current 
that is determined, is carefully checked and if required, appropriately corrected. 
START 
P0625 = ? 
20 °C
 
| Motor temp. - P0625| 
≤  5 °C ? 
Allow the motor  
to cool down 
P1910 = 1 
0
 
A0541 
ON 
OFF1 
P1910 = 3 
0
 
A0541 
ON 
OFF1 
END