Hitachi L2002 User Manual
L200
2
Inverter
Appendix B
B–19
ModBus Data Listing
ModBus Coil List
The following tables list the primary coils for the inverter interface to the network. The
table legend is given below.
table legend is given below.
• Coil Number - The network register address offset for the coil, in hex and decimal.
Actual network address is 30001 + offset. The coil data is a single bit (binary) value.
• Name - The functional name of the coil
• R/W - The read-only (R) or read-write (R/W) access permitted to the inverter data
• Description - The meaning of each of the states of the coils
List of Coil Numbers
Coil Number
Name
R/W
Description
hex
dec.
0000h
00000 (Reserved)
R
—
0001h
00001 Run command
R/W
0 .... Stop
1 .... Run (enabled when A003=03)
1 .... Run (enabled when A003=03)
0002h
00002 FW/REV command
R/W
0 .... REV
1 .... FW (enabled when A003=03)
1 .... FW (enabled when A003=03)
0003h
00003 External trip (EXT)
R/W
0 .... No trip event
1 .... Trip occurred
1 .... Trip occurred
0004h
00004 Trip reset (RS)
R/W
0 .... No reset condition
1 .... Reset
1 .... Reset
0005h
00005 (Reserved)
R
—
0006h
00006 (Reserved)
R
—
0007h
00007 Intelligent input terminal 1
R/W
0 .... OFF *1
1 .... ON
1 .... ON
0008h
00008 Intelligent input terminal 2
R/W
0009h
00009 Intelligent input terminal 3
R/W
000Ah 00010 Intelligent input terminal 4
R/W
000Bh 00011 Intelligent input terminal 5
R/W
000Dh 00013 (Not used)
—
—
000Eh
00014 Run/Stop status
R
0 .... Stop (corresponds to D003
monitor)
1 .... Run
monitor)
1 .... Run
000Fh
00015 FW/REV status
R
0 .... FW
1 .... RV
1 .... RV
0010h
00016 Inverter ready
R
0 .... Not ready
1 .... Ready
1 .... Ready
0011h
00017 (Reserved)
R
—
0012h
00018 (Reserved)
R
—