Appendix A  Product Agency Approvals, Standards, and General Specifications 
A-3 
A
 
  
 
General Specifications 
 GENERAL 
SPECIFICATIONS 
Standard(s) 
Conditions 
  ISOLATION 
 
 
   Dielectric 
Withstand 
UL 508, UL 840, 
IEC 664 
1.5KV DC (input power to secondary outputs) 
 ENVIRONMENTAL 
 
 
   Vibration 
IEC 68-2-6 
10 - 57 Hz, 0.012" displacement peak-peak 
57 - 500 Hz, 1.0g acceleration  
   Shock 
IEC 68-2-27 
15g, 11ms, sinusoidal  
   Operating 
Temperature 
 
0°C to 50°C 
   Storage 
Temperature 
 
-20°C to +60°C 
   Humidity 
 
5% to 95% RH (non-condensing) 
   Enclosure 
Protection 
NEMA 250 
NEMA Type 4, 4x and 12 when mounted in panel 
  EMC EMISSIONS 
 
[applies to CE Marked units] 
   Radiated, 
Conducted 
CISPR 11/EN 55011 “Industrial Scientific & Medical Equipment” 
(Group 1, Class A) 
   
CISPR 22/EN 55022 “Information Technology Equipment” (Class A) 
   
47 CFR 15 
referred to as FCC part 15, “Radio Devices” (Class A) 
         Harmonics 
EN 61000-3-2 
Class D 
  EMC IMMUNITY 
 
[applies to CE Marked units] 
   Electrostatic 
Discharge 
EN 61000-4-2 
±8KV Air, ±4KV Contact 
   RF 
Susceptibility 
EN 61000-4-3 
10Vrms /m, 80Mhz to 1000Mhz, 80% AM, 1kHz sine wave 
   
 
ENV 50140/ 
ENV 50204 
10Vrms /m, 900 ± 5Mhz, 100% PM, 200Hz square wave 
   
Fast Transient Burst 
EN 61000-4-4 
 
±2KV: AC Input Port 
 
±1KV: Signal Ports 
   Surge 
Withstand 
EN 61000-4-5 
±2KV (12Ω) CM, ±1kV (2Ω) DM: AC Input Port 
±1kV (2Ω) CM: Signal Ports (shielded) 
   
 
ANSI C37.90A 
+2.5KV CM & DM: AC Input Port 
+2.5KV CM: Signal Ports (shielded) 
   Conducted 
RF 
 
EN 61000-4-6 
10Vrms, 0.15 to 80Mhz, 80%AM: AC Input & Signal Ports 
   
Input Dips & Variation   
EN 61000-4-11 
AC Input Dips: 30 & 100% Nominal (10ms) 
AC Input Variation: ±10% Nominal (10s) 
   Voltage 
Flicker 
 
EN 61000-3-3 
D
t
 < 3.3%, D
c
 < 3.3%, D
max
 < 4.0%, P
st
 < 1.0: AC Input Port