Siemens D410 User Manual
Configuring SIMOTION D410
3.4 Configuring PROFINET (only for D410 PN)
D410
Commissioning Manual, 08/2008 Edition
Commissioning Manual, 08/2008 Edition
53
3.4.2
Operating SIMOTION D410 PN on PROFINET
PROFINET interfaces (X200, X201)
SIMOTION D410 PN provides a dual-port PROFINET interface (X200 and X201). The
interface supports transmission rates as high as 100 Mbit/s. It can also be operated
isochronous and equidistant. The autocrossing functionality means both crossed and
uncrossed cables can be used
A port has two integrated LEDs, a green LED and an orange LED. The following LED states
A port has two integrated LEDs, a green LED and an orange LED. The following LED states
can occur:
Table 3-3
LED states of the LED on the port of the PROFINET interface
LEDs
State
Meaning
Green
LED off
No connection to an active partner exists.
LED on
A connection to an active partner exists.
Orange
LED off
No data is being exchanged.
LED flashing
Data is being exchanged over the port.
The LED flashes irregularly depending on the data
The LED flashes irregularly depending on the data
exchange,
i.e. the LED does not flash with a specific frequency.
Properties of PROFINET on SIMOTION D410 PN
SIMOTION D410 PN on PROFINET supports the following properties
● PROFINET specifies operation at 100 Mbit/s.
● The minimum send cycle is 0.5 ms, and the maximum is 4 ms.
● The setting accuracy for the send cycle is 125 μs.
The use of cycle reduction is possible for the D410. Detailed information concerning cycle
● PROFINET specifies operation at 100 Mbit/s.
● The minimum send cycle is 0.5 ms, and the maximum is 4 ms.
● The setting accuracy for the send cycle is 125 μs.
The use of cycle reduction is possible for the D410. Detailed information concerning cycle
reduction is available in the SIMOTION SCOUT Communication System Manual.