Network Management Card & Modbus/Jbus                                                                                        34022321XT indice :AE            Page 79/98 
Network Management Teleservice Card 
                 
APC by Schneider Electric  
www.apc.com 
Description of the physical quantity 
Word (hex) 
Unit 
Data 
type 
Battery temperature (Nota 1) 
14A 
°C 
unsigned 
Battery charging level (Nota 1) 
14B 
unsigned 
U AC normal (phase 1) (Nota 1) 
150 
unsigned 
U AC normal (phase 2) (Nota 1) 
151 
unsigned 
U AC normal (phase 3) (Nota 1) 
152 
unsigned 
Number of battery block (Nota 1) 
153 
unsigned 
Total battery capacity (Nota 1) 
154 
Ah 
unsigned 
Nominal Apparent Power 
209 
kVA 
unsigned 
Nominal battery voltage (Nota 1) 
213 
unsigned 
 
Nota1 :  This Information is not present in a Static Switch Cabinet. 
Nota2 :  For a configuration with UPS in parallel with SCC unit, the Main 2 data need to read on the card installed in the SSC unit.  
10.3.3 Environnement Sensor Table 
10.3.3.1 Sensor Status table 
Status description 
Status to 0 
Status to 1 
Word (hex) 
Bit 
0 - F 
Communication fault 
no 
Yes 
45 
Alarm : temperature too high 
no 
Yes 
45 
Alarm : temperature too low 
no 
Yes 
45 
Alarm : humidity too high 
no 
Yes 
45 
Alarm : humidity too low 
no 
Yes 
45 
Input 1 alarm 
no 
Yes 
45 
Input 2 alarm 
no 
Yes 
45 
Input 1 
open 
Closed 
48 
Input 2 
open 
Closed 
48 
10.3.3.2 Sensor Measurements table 
Description of the physical quantity 
Word (hex) 
Unit 
Temperature measure 
180 
°C 
Maximum temperature 
181 
°C 
Minimum temperature (°C) 
184 
°C 
Humidity measure (%) 
187 
Maximum humidity (%) 
188 
Minimum humidity (%) 
18B