DataNET Troubleshooting Guide, 
Continued 
 
Configuration 
Parameter Errors 
The device may have an invalid or duplicate IP address, Subnet mask or 
iproute. Each ANCB must have a unique IP address. Verify the 
configuration parameters by connecting a PC serial port to the 
Configuration Port, Logging in and typing config display
local> config display 
   Config: 
     Device 
ANCB_DN 
     address ip 
172.16.9.239 
     netmask 
255.255.0.0 
     address ethernet 
00.c0.c9.00.d2.3b 
     iproute 
0.0.0.0 
     time server ip 
0.0.0.0 
     port1 
DataNET Copper 
     port2 
DataNET Copper 
 
Device ID 
The ANCB/DN device id is automatically assigned and is not user 
configurable as it is on the DataNET Hub. Th ANCB/DN device ID is 
automatically set to the board IP address at power up or reset. : 
 
Broadcast Status 
Information 
The Advance Network device periodically broadcast their status for 
diagnostic and network routing purposes. 