To change settings, remove the Philips screw on the front of the 3M™ Macurco™ GD-6 Combustible Gas Detector. Pull off the 
front cover of the unit.
Gas Selection
To select the 
Gas option, in normal mode, press the Next button once to display the current gas selection (mE is Methane, 
pro is propane and Hy is Hydrogen). Then press the Enter button twice to enter the selection menu. The currently selected 
gas will be shown on the display. Press 
Next to scroll through the available gases selections. The selected gas will be flashing, 
press 
Enter to select the gas and Enter again to confirm the selection. To return back to normal mode press Next until “End” is 
displayed and press 
Enter.
Selecting Default Configuration – “dEF”
To select the Default Configuration, in normal mode, press the 
Next button twice to get to “Con” or the Configuration menu. 
Then press the 
Enter button to enter the Con menu. The first selection is the “dEF” or Default setting. Press Enter. If it is 
already in Default configuration, there will be no action. If it is not already in Default configuration, “nO” will be displayed. Press 
Next to change it to “YES” (flashing) then press Enter to confirm the change (solid) and press Enter again to return to “dEF” in 
the Con menu. Press 
Next until “End” is displayed then press Enter to return to normal operation. 
Selecting power Up Test option – “pUt”
To select the 
power Up Test Configuration, in normal mode, press the Next button twice to get to “Con” or the Configuration 
menu. Then press the 
Enter button to enter the Con menu. Then press the Next button to get to the second selection “PUt” 
or 
power Up Test setting. Press Enter. If the test is “On” press Next to turn it “OFF” (flashing) then press Enter to confirm the 
change (solid) and press 
Enter again to return to “PUt” in the Con menu. Press Next until “End” is displayed then press Enter 
to return to normal operation. 
Selecting Display option – “dSp”
To select the Display Configuration, in normal mode, press the 
Next button twice to get to “Con” or the Configuration menu. 
Then press the 
Enter button to enter the Con menu. Then press the Next button twice to get to the third selection “dSP” or 
Display setting. Press 
Enter. If the display is “On” press Next to turn it “OFF” (flashing) then press Enter to confirm the change 
(solid) and press 
Enter again to return to “dSP” in the Con menu. Press Next until “End” is displayed then press Enter to return 
to normal operation. 
Selecting Buzzer option – “bUZ”
To select the Buzzer Configuration, in normal mode, press the 
Next button twice to get to “Con” or the Configuration menu. 
Then press the 
Enter button to enter the Con menu. The fourth selection is the “bUZ” or Buzzer setting. Press Next three 
times to get to “bUZ” then press 
Enter. If the display is “On” press Next to turn it “OFF” (flashing) then press Enter to confirm 
the change (solid) and press 
Enter again to return to “bUZ” in the Con menu. Press Next until “End” is displayed then press 
Enter to return to normal operation. 
Selecting alarm relay Setting – “arS”
To select the Alarm Relay Setting, in normal mode, press the 
Next button twice to get to “Con” or the Configuration menu. Then 
press the 
Enter button to enter the Con menu. The fifth selection is the “ArS” or Alarm Relay Setting. Press Next four times to 
get to “ArS” then press 
Enter. If the display is “OFF” (disabled) press Next to change it to 5, 10, 15, 20 or 25% LEL (flashing) 
then press 
Enter to confirm the change (solid) and press Enter again to return to “ArS” in the Con menu. Press Next until “End” 
is displayed then press 
Enter to return to normal operation. 
Selecting alarm relay Configuration – “arc”
To select the 
alarm relay Configuration, in normal mode, press the Next button twice to get to “Con” or the Configuration 
menu. Then press the 
Enter button to enter the Con menu. The sixth selection is the “Arc” or Alarm Relay Configuration. Press 
Next five times to get to “Arc” then press Enter. If the relay is “nO” (normally open) press Next to turn it to “nC” (flashing) then 
press 
Enter to confirm the change (solid) and press Enter again to return to “Arc” in the Con menu. Press Next until “End” is 
displayed then press 
Enter to return to normal operation. 
Selecting Fan relay Settings – “FrS”
To select the Fan Relay setting, in normal mode, press the 
Next button twice to get to “Con” or the Configuration menu. Then 
press the 
Enter button to enter the Con menu. The seventh selection is the “FrS” or Fan Relay setting. Press Next six times 
to get to “FrS” then press 
Enter. If the fan relay is “OFF” (disabled) press Next to change it to 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 
13, 14, 15, 16, 17, 18, 19 or 20% LEL (flashing) then press 
Enter to confirm the change (solid) and press Enter again to return 
to “run” in the Con menu. Press 
Next until “End” is displayed then press Enter to return to normal operation. 
Selecting Fan relay Delay – “FrD”
To select the Fan Relay Delay setting, in normal mode, press the 
Next button twice to get to “Con” or the Configuration 
menu. Then press the 
Enter button to enter the Con menu. The eighth selection is the “FrD” or Fan Relay Delay. Press Next 
seven times to get to “FrD” then press 
Enter. If the delay is “OFF” (disabled) press Next to change it to 1, 3, 5, or 10 minutes 
(flashing) then press 
Enter to confirm the change (solid) and press Enter again to return to “FrD” in the Con menu. Press Next 
until “End” is displayed then press 
Enter to return to normal operation.