Honeywell MRP-2001 User Manual
Circuit Mapping and Cross-Zoning
Input-to-Output Circuit Mapping and Cross-Zone Operation
104
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007
A.1.1 Mapping Input Zones to Output Circuits for Direct Activation
Using the INPUT ZONES menus, you can assign any input zone to directly activate (without cross-
zoning) any of the four output circuits provided they are assigned matching operational types (see
the OUTPUT CIRCUIT MAP menu within the INPUT ZONES menus).
zoning) any of the four output circuits provided they are assigned matching operational types (see
the OUTPUT CIRCUIT MAP menu within the INPUT ZONES menus).
Example 1: A waterflow input zone assigned to directly activate an alarm output circuit by setting
the OUTPUT CIRCUIT MAP assignment to YES.
the OUTPUT CIRCUIT MAP assignment to YES.
•
Output Circuit 1 is programmed as alarm NAC using the OUTPUT CIRCUITS menus.
•
Output Circuit 2 is programmed as Release Circuit 1 using the OUTPUT CIRCUITS menus.
•
Output Circuit 3 is programmed as Release Circuit 2 using the OUTPUT CIRCUITS menus.
•
Output Circuit 4 is programmed as supervisory NAC using the OUTPUT CIRCUITS menus.
•
Input Zone 1 is programmed as a waterflow zone using the INPUT ZONES menus.
Waterflow Input Zone 1 will directly activate Output Circuit 1 (Alarm NAC) but not Output
Circuits 2, 3 or 4.
Circuits 2, 3 or 4.
Example 2: A single hazard application where a smoke detector input zone will directly activate
both an alarm NAC circuit and a releasing output circuit.
both an alarm NAC circuit and a releasing output circuit.
•
Output Circuit 1 is programmed as alarm NAC using the OUTPUT CIRCUITS menus.
•
Output Circuit 2 is programmed as Release Circuit 1 using the OUTPUT CIRCUITS menus.
•
Output Circuit 3 is programmed as waterflow NAC using the OUTPUT CIRCUITS menus.
•
Output Circuit 4 is programmed as supervisory NAC using the OUTPUT CIRCUITS menus.
•
Input Zone 1 is programmed as a smoke detector zone using the INPUT ZONES menus.
Smoke detector Input Zone 1 will directly activate Output Circuits 1 (Alarm NAC) and 2 (Release
1) but not output circuits 3 or 4.
1) but not output circuits 3 or 4.
ZONE 1 TYPE
1=N/A
2=WATERFLOW
3=WATERFLOW NS
1=N/A
2=WATERFLOW
3=WATERFLOW NS
OUTPUT MAP ZONE 1
1=ALARM NAC YES
2=RELEASE 1 NO
3=RELEASE 2 NO
1=ALARM NAC YES
2=RELEASE 1 NO
3=RELEASE 2 NO
OUTPUT MAP ZONE 1
1=SUPV BELL NAC N/A
1=SUPV BELL NAC N/A
ZONE 1 TYPE
1=COMBO
2=COMBO W/AR. SUPERV
3=2-WIRE SMOKE
1=COMBO
2=COMBO W/AR. SUPERV
3=2-WIRE SMOKE
OUTPUT MAP ZONE 1
1=ALARM NAC YES
2=RELEASE 1 YES
3=WATERFLOW NAC NO
1=ALARM NAC YES
2=RELEASE 1 YES
3=WATERFLOW NAC NO
OUTPUT MAP ZONE 1
1=SUPV BELL NAC N/A
1=SUPV BELL NAC N/A