Page 34
SITRANS LR 460 – INSTRUCTION MANUAL 
7ML19985JM01
m
mmmm
Qui
c
k S
tart
Level application example
The application is a steel silo containing flour that takes an average 3 hours to fill and 3 
weeks to empty.
 
Using the Easy Aimer, the LR 460 is oriented so that the emission cone is approximately 
perpendicular to the material surface.
Fill rate = 0.09 m/minute (15.5 / 180). Response rate has been set to slow: 0.1 m/minute, or 
slightly faster than the fill rate.
Quick Start Setting
Description
Language
ENGLISH
Application Type
STEEL
Silo construction
Operation
LEVEL
Material level referenced from Low Calibration point.
Units
m
High Calibration Point
1.0
Process full level.
Low Calibration Point
15.5
Process empty level.
Rate
SLOW
Response rate = 0.1 m/minute.
Apply Changes
YES
Save new settings.
SITRAN
S LR 40
0
Sensor Reference Point
(flange face)
Level 
Low Calibration Point
High Calibration Point
15.5 m
1.0 m
LR 460 with Easy Aimer